Technical Overview & Specification
Use this quick reference field checklist before leaving the installation site to guarantee 100% operational success and instant network connectivity.
1. Phase 1: Physical & Electrical Verification
Verify ground loop resistance is below 10 Ohms. Confirm 400V line-to-line and 230V line-to-neutral measurements. Ensure Type B RCD is armed.
2. Phase 2: Firmware & Communication Test
Power up station and confirm green status LED. Verify cellular signal RSSI is stronger than -85 dBm. Confirm WebSocket handshake with WATT.ma.
3. Phase 3: Live Session Test & Handoff
Tap test RFID card, plug vehicle or simulator, and confirm charging current initiates within 5 seconds. Send sign-off photos to support@watt.ma.
Compliant with Moroccan national grid (ONE), CNDP Law 09-08 data protection, and international OCPP standards.